14. Troubleshooting

Version 1.2Software: FuelTech Vision 3.0Firmware: 00.03.00.01Products: FT700, FT470, VisionFT2026-10-13

#Diagnostic tools

#Symptoms, causes and solutions

SymptomProbable causeWhat to do
Nothing arrives: the channel stays at zero and the sniffer does not show the IDPort off; mode or rate different from the module's; CAN_H and CAN_L swapped; module without power; module on another portCheck CAN ports (port on, mode, rate). Measure the 60 Ω. Check the wiring and the module's power. On the FT700, test the other ports in the sniffer.
The sniffer shows the ID, but the channel stays at zeroBytes of the RX frame greater than the real size; ID different from what the module transmits; Direction still TX after importing a DBC; frame or function off; frame disabled by an errorSet Bytes to the size seen in the sniffer. Check the ID and the Direction. See the "Custom CAN: Frame error" channel.
Nonsensical value, very large or jumping aroundByte order swapped; wrong Start bit; wrong signed/unsigned settingSwap Intel/Motorola. Redo the position from the DBC. Check the Value type.
Value stuck at the offset or at zero, with no errorArithmetic channel off with a scale below 1Turn Arithmetic channel on.
The value drops to zero from time to timeTimeout too short for the sender's periodUse a Timeout of at least three times the sender's period and never less than 0.5 s.
Value one step lower than expectedThe VCU truncates the raw value when transmittingIf the receiving equipment lets you choose the scale, use a finer one (0.1 instead of 1) and the same one on both sides: Scale and Offset in the VCU must match the receiver's. If it does not, use the scale the equipment specifies: the truncation is normal.
The third-party equipment receives nothingStandard vs extended ID swapped; wrong port or rate; FD frame to classic equipmentCheck Extended ID and the port. On an FD port, turn on Force classic CAN in the frame.
"Communication error - CAN A" notificationThe VCU cannot transmit on the port. Two causes: a port checked in Alerts > Error in the CAN port with no acknowledgment of the frames for longer than the time for validation; or a failure of the port itself, which the VCU restarts in about 1 sCheck whether another module is connected and powered, the rate and the wiring. If the port is not checked in the alert, the cause is the port failure: check the electrical connections and the harness.
"CAN A: Bus error" notificationExcessive errors (bus-off): different rate, wrong termination, swapped or shorted wiresMeasure the termination, check the rate of all modules and the wiring.
"Error initiating Can port B" notificationFD mode on a port that does not support CAN FD, or invalid rateTurn FD mode off (see which ports accept FD in the ports chapter) and turn the VCU off and back on.
"CAN A Disabled" notificationThe port is off in CAN portsIf the port should be in use, turn it on, then turn the VCU off and back on.
FuelTech device does not appear in CAN NetworkPort in RAW mode; port off; termination; two identical devices with the same identification on the networkSet the port to FTCAN 2.0, turn it on, then turn the VCU off and back on. Check the termination and the identification of each device.
You changed the rate, mode or terminator and nothing changedThe port is only reconfigured at power-upWrite the map, turn the VCU off and back on.
CAN: Bus load above about 70% (rule of thumb)Heavily loaded bus: delays and lost frames. Without acknowledgment of the frames the load also appears highIncrease the periods, turn off what is not used, move devices to another port.